Egressconcept

Means of egress: exit access, exit, exit discharge

One-line orientation

A means of egress is the code-defined route out of a building. It has three parts: exit access, exit, and exit discharge. The middle part is the protected exit, and protection increases along the route to the street.

Key points

  • A means of egress has three parts, in sequence:
    • Exit access — the travel from any point in the building to an exit. Rooms and corridors fall here; it is the least-protected leg.
    • Exit — the protected, fire-rated portion: an enclosed (rated) stair or an exterior exit door. This leg is separated from the rest of the building by rated construction.
    • Exit discharge — from the exit to the public way (street / public right-of-way). The final leg.
  • Safety increases along the path: each part must be as safe or safer than the previous part — never a step down in protection as you head toward the street.
  • Fire ratings step up as you move from unit → corridor → stairwell.
  • Egress-path door rules support the route. Doors must be openable from the egress side without a key or special knowledge. A door must swing in the direction of egress travel when it serves 50 or more occupants or a Group H occupancy.

Means of egress — one continuous path, three code-defined parts

Exit access → protected exit → exit discharge to the public way

View diagram Hide diagram

Scroll horizontally to explore

The three parts of a means of egress shown in a building section An original longitudinal building section shows occupied rooms and corridors at left, a double-wall blue rated stair enclosure at center, and exterior grade leading to the public way at right. One continuous arrowed route begins at any point on the upper occupied floor, crosses the corridor as exit access, enters the protected stair and descends through two switchback flights as the exit, then continues at grade across the yard or walkway as exit discharge to the public way. Direct labels above and below identify all three components. The double blue stair wall and stair geometry redundantly identify the protected middle leg. Protection is drawn as a three-rung ladder rising toward the street: the unit is labeled lower fire rating behind a light interior partition, the corridor is labeled higher fire rating behind a heavier unit-to-corridor wall, and the stair enclosure is labeled highest fire rating behind its double blue rated wall. EXIT ACCESSEXITEXIT DISCHARGEany pointunitcorridorlower fire ratinghigher fire ratingoccupied flooroccupied floorRated enclosurehighest fire ratingexterior walkwaypublic wayany point → protected exitprotected leg onlyexit → public way

Protection increases toward the street: each part as safe or safer than the one before, unit → corridor → stair.

Confusions / comparison

PartWhere it isProtectionCommon confusion
Exit accessAny point in the building → the exitLeast protected (rooms, corridors)People call the whole route the “exit” — this is only the access
ExitThe protected/rated portion onlyRated: enclosed stair or exterior doorThe exit is just this leg, not the path from your desk to the street
Exit dischargeExit → public wayLeads to a safe place outsideConfused with the exit itself; it is the leg after the exit

→ Number of exits and exit separation (this topic): how many of these routes are required and how far apart · Common path vs travel distance vs dead-end (this topic): how the exit-access leg is measured · Corridors (this topic): the rated exit-access corridor.